A few things you should know before using the Remote Sensing function.

First, use twisted wires, connect +S to the positive end of the output, then -S to the negative end of the output, as shown in the illustration. Also, keep the wires off the AC and output cables to prevent noise interference.

Add capacitors at the output end where the Remote Sensing wires are connected to if the dynamic load (frequency above 1K Hz) is used. The purpose is to reduce noise as Remote Sensing is a sensitive function. A suitable capacitor requires two factors:

a. Rated Ripple Current is 0.2 times greater than the output current

b. Rated Voltage is higher than the output voltage

Categories: Industrial, Operation
Tag: Remote Sensing